Evaluations — Input View

Evaluations for input

1 rows

Input
Output
Evaluation Input Image

A room is kept at 25°C by a vapor-compressionrefrigeration cycle with R-134a as the refrigerant. Heat is rejected to cooling water that enters the condenser at 20°C at a rate of 0.13 kg/s and leaves at 28°C. The refrigerant enters the condenser at 1.2 MPa and 50°C and leave as a saturated liquid. If the compressor consumes 1.9 kW of power, determine the exergy destruction in the condenser. Take T0 = 20°C and cp,waterc_{p,water} = 4.18 kJ/kg⋅°C<image 1>



(A) 0.1 kW


(B) 0.2 kW


(C) 0.3 kW


Answer with the option's letter from the given choices directly. No punctuation.


A


Expected Answer: C

Difficulty: Medium

Subfield: Thermodynamics

Input

Input ID
3289d37c-8331-402a-bc7b-53715e57e3f6
Created
February 15, 2024
Permission
Public